Repository logo
Log In(current)
  1. Home
  2. Colleges & Schools
  3. Graduate School
  4. Masters Theses
  5. Simultaneous removal of sulfur oxides and particulate matter from stoker-fired boiler flue gas with a pilot plant fabric filter collector
Details

Simultaneous removal of sulfur oxides and particulate matter from stoker-fired boiler flue gas with a pilot plant fabric filter collector

Date Issued
August 1977
Author(s)
Keener, Timothy C.
Advisor(s)
Wayne T. Davis
Additional Advisor(s)
D. W. W.
R. B.
Permanent URI
https://trace.tennessee.edu/handle/20.500.14382/59220
Abstract

A research effort has been undertaken in which the simultaneous removal of particulates and SO2 was studied, A pilot plant fabric filter test unit was installed on a spreader-stoker coalfired boiler and an extensive test program was undertaken to determine the efficiency of particulate and S02 removal without additive injection. Second, a gaseous additive, NH3, was injected into the flue gases leading to the pilot plant and a series of tests was performed to establish the relationship between S02 as removal efficiency, the amount of NH3 injected, and the fabric filter collector's operating temperature.

The results of the testing program showed that the fabric filter (without additive injection) removed 25% of the S02 from the inlet gas stream between the temperatures of 140°-260°F, with particulate removal efficiencies of 99% or greater. This corresponded to reductions in the flue gas concentrations of 200-500 ppm. With the injection of NH3, it was possible to achieve 96-99% overall removal efficiencies of S02, for operating temperatures of less than 190° F at mole ratios of NH3/S02 of 0.70-0.75. For the temprature range of 190°F to 260° F, the S02 removal efficiency was limited by the appearance of a visible plume at mole ratios of NH3/S02 greater than approximately 0.25. At that mole ratio, however, it was possible to obtain S02 removal efficiencies of approximately 50%. Further studies are being conducted to determine the dependence of SO2 removal efficiency on temperatures greater than 260° and to determine the chemical composition of the reactants formed.

 
Degree
Master of Science
Major
Environmental Engineering
File(s)
Thumbnail Image
Name

Thesis77.K335.pdf

Size

2.73 MB

Format

Adobe PDF

Checksum (MD5)

e2680074d9b657995807278b601a70c3


University Libraries

1015 Volunteer Boulevard
Knoxville, TN 37996
865-974-4351

Map & Directions
Donate to the Libraries
  • About
  • John C. Hodges Society
  • Speaking Volumes magazine
  • Outreach
  • Directory
  • Employment
  • Policies
  • Library Intranet
University of Tennessee power T logo

The University of Tennessee, Knoxville
Knoxville, Tennessee 37996
865-974-1000

Events
A-Z
Apply
Privacy
Map
Directory
Give to UT
Accessibility

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science