Repository logo
Log In(current)
  1. Home
  2. Colleges & Schools
  3. Graduate School
  4. Masters Theses
  5. In-situ response time testing of platinum resistance thermometers in nuclear power plants
Details

In-situ response time testing of platinum resistance thermometers in nuclear power plants

Date Issued
December 1977
Author(s)
Hashemian, Hashem Mehrdad, 1950-
Advisor(s)
T. W. Kerlin
Additional Advisor(s)
P. F. Pasqua
Lawrence F. Miller
E. Maria Katz
Permanent URI
https://trace.tennessee.edu/handle/20.500.14382/59120
Abstract

Coolant temperature sensors are components of the safety systems of nuclear power plants, and the rate of their response to a coolant temperature change is important in determining the overall time for safety system actuation. This study presents the development of equipment and techniques for in-situ response time verification of platinum resistance thermometers used in modern pressurized water reactors for measurement of coolant temperatures. A method called the loop current step response test was employed for quantitative evaluation of the response time of temperature sensors after installation in a plant. The application of this method on resistance thermometers is based on monitoring a temperature transient that results from a step change in electric current through the sensing filament. This transient is analyzed to provide the desired response time.

Another method called the self heating test was used for diagnosis of sensor response time degradation. This method is based on the steady state measurement of the temperature rise in a sensor as a function of electric power input. The temperature rise per unit of electric power depends on the heat transfer characteristics of the sensor, thus a change in the heat transfer characteristics and, therefore, a change in the response time of a sensor can be detected by the seif heating test.

The results of laboratory testing of seven different platinum resistance thermometers and in-plant response time testing in three nuclear power stations indicated that the methods are adequate for the verification of response time of installed temperature sensors.

 
Degree
Master of Science
Major
Nuclear Engineering
File(s)
Thumbnail Image
Name

Thesis77.H279.pdf

Size

20.91 MB

Format

Adobe PDF

Checksum (MD5)

72675491d76feddf4e064a869c0073d9


University Libraries

1015 Volunteer Boulevard
Knoxville, TN 37996
865-974-4351

Map & Directions
Donate to the Libraries
  • About
  • John C. Hodges Society
  • Speaking Volumes magazine
  • Outreach
  • Directory
  • Employment
  • Policies
  • Library Intranet
University of Tennessee power T logo

The University of Tennessee, Knoxville
Knoxville, Tennessee 37996
865-974-1000

Events
A-Z
Apply
Privacy
Map
Directory
Give to UT
Accessibility

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science