Simplified reliability calculations for distribution systems
The object of this thesis was to develop a simplified method for analyzing power substation designs on a reliability versus cost basis and to apply this method to an existing system. The system to which this was applied is the Nashville Electric Service 161kV to 23.9kV distribution system.
Three substation designs were selected as applicable to this system and a probability model for these was developed using the conditional probability equation and the approximate method of combining system probabilities. A 69kV design that has given acceptable service for many years was also analyzed for reference.
Data for use in these models was compiled and includes 69kV and 161kV transmission line outage rates and durations and data applicable to 23.9kV, 69kV and 161kV substation components.
Although the results of this study indicate that a Main and Transfer Bus design with oil circuit breaker similar to existing 69kV designs offers the only improvement in reliability sone savings can be effected by using a design with motor operated switching but with marginal decrease in reliability.