Development of methods for in situ testing of response times of resistance temperature detectors in commercial pressurized water reactors
Resistance temperature detectors (RTD's) are used in nuclear plant safety systems to measure process temperatures. The purpose of this research was to develop and evaluate suitable methods for in situ testing of the response time of RTD's.
Three testing procedures were used in laboratory experiments: (1) loop current step response (LCSR) test, (2) self-heating test, and (3) plunge test. The LCSR test involved a step change in the internal ohmic heating of a sensor. The self-heating test involved measurement of steady state temperature changes due to incremental changes in ohmic heating current. The plunge test was used to approximate a fluid temperature step response.
The LCSR results were compared to plunge test results through use of an analytical transformation. Because the physical makeup of the sensor used in the laboratory testing did not conform to the assumptions required in the heat transfer model used in the transformation, the transformation failed.
Empirical transformations were developed using the LCSR, self-heating, and plunge tests. The correlation curves that were developed were used to predict sensor plunge test time constants.
Finally, time response testing was conducted at Turkey Point Nuclear Plant and results obtained are discussed.
Results from the laboratory testing indicate that the LCSR and self-heating tests are valid procedures for predicting response times of resistance temperature detectors.