Repository logo
Log In(current)
  1. Home
  2. Colleges & Schools
  3. Graduate School
  4. Doctoral Dissertations
  5. Protection System Design and Engineering for Safe and Reliable Transmission System Operation
Details

Protection System Design and Engineering for Safe and Reliable Transmission System Operation

Date Issued
May 2026
Author(s)
Kobet, Gary
The University of Tennessee
Advisor(s)
Yilu Liu
Additional Advisor(s)
Russell Patterson
Kevin Bai
Kai Sun
Permanent URI
https://trace.tennessee.edu/handle/20.500.14382/57660
Abstract
A 35-year career as a field and staff engineer has provided extensive experience in the design, operation, and analysis of a 30,000+ MW power system spanning transmission, distribution, and generation. Over this period, the author has developed expertise in fault and event analysis, switching reviews, and generator control and response. The work also included, in large part, protection and control engineering across a wide range of equipment (e.g., transmission lines, buses, transformers, reactors, capacitor banks, and generators)), together with the study of key power-system phenomena such as ferroresonance, surge-impedance loading, the Ferranti effect, capacitor-bank switching, and transient-recovery voltage. A recurring theme has emerged from this experience: design engineers often overlook their primary customer, the system operator. The system operators considered herein include (1) the Transmission Operator (TOp), responsible for system restoration following unplanned breaker operations to lock out, as well as preparing planned and emergency switching orders to provide safe working clearances; and (2) the field operator, who executes those switching orders. Choices in switchyard layout and associated protection schemes critically influence the operator’s ability to understand station configuration, execute accurate switching, and maintain system safety. When these considerations are neglected, the result can elevate operational complexity, reduce reliability, and increase risk to field personnel. Five of the articles in this dissertation examine specific cases where design practices failed to adequately account for system-operator needs. These cases involve relay loadability, ungrounded tertiary bus ground-fault protection (alarm versus trip philosophies), tertiary shunt reactor protection, ferroresonance, and the Ferranti effect. In each instance, the author recommends improvements aimed at enhancing operator situational awareness, clarifying protection-scheme behavior, and ensuring that the system is left in a safe state for field personnel. The remaining four articles highlight expertise developed in post event analysis and transmission system protection engineering. One article (Chapter VI) discusses the significant hazards associated with conducting primary switching operations while primary protection is disabled. Another article (Chapter VIII) illustrates the operational challenges of restoring load following voltage collapse driven by inadequate transmission support. The final two articles (Chapters VI and IX) demonstrate how rigorous post-event analysis can drive meaningful improvements in protection system engineering and operational performance.
Subjects

Power systems, protec...

Protection

control

system operator

station configuration...

switching

safety

reliability

transmission

Degree
Doctor of Philosophy
Major
Electrical Engineering
File(s)
Thumbnail Image
Name

KOBET-PRIMARY-2026.pdf

Size

8.47 MB

Format

Adobe PDF

Checksum (MD5)

0b6d410f6a02354ae3fe44ff18895208


University Libraries

1015 Volunteer Boulevard
Knoxville, TN 37996
865-974-4351

Map & Directions
Donate to the Libraries
  • About
  • John C. Hodges Society
  • Speaking Volumes magazine
  • Outreach
  • Directory
  • Employment
  • Policies
  • Library Intranet
University of Tennessee power T logo

The University of Tennessee, Knoxville
Knoxville, Tennessee 37996
865-974-1000

Events
A-Z
Apply
Privacy
Map
Directory
Give to UT
Accessibility

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science