Performance of a Ground-Coupled Heat Pump during a Cooling Season

Date Issued
June 1, 1984
Author(s)
Wix, Steven D.
Advisor(s)
W.S. Johnson
Additional Advisor(s)
J.R. Parsons
Rao V. Arimilli
Permanent URI
https://trace.tennessee.edu/handle/20.500.14382/39235
Abstract

A ground-coupled heat pump system was installed in TECH House I at the Tennessee Energy Conservation in Housing site located on the University of Tennessee campus. The performance of the heat pump system was evaluated for the cooling season of 1983. Data on system energy flows, power consumption, house temperatures, soil temperatures and weather conditions were gathered on an hourly basis for the entire cooling season. Weekly coefficients of performance, soil thermal conductivitys, and a seasonal performance factor were calculated from experimental data.


The performance was found to be poor when compared to a conventional air-to-air heat pump system. The seasonal performance factor for the ground-coupled heat pump system was 1.11 while typical conventional heat pump system seasonal performance factors for the Knoxville area are around 2.3. A trend of performance deterioration over the season due in part to decreasing soil thermal conductivity was found. The decreasing soil thermal conductivity was caused by a decrease in soil moisture.

The ground-coupled heat pump system was modeled using the TRNSYS and GROCS computer programs. Comparison with experimental data validated the computer model. The difference between the predicted and experimental seasonal performance factors was approximately 3 percent.

Parametric studies were performed to determine system performance under various conditions. Factors varied include soil moisture content, density, cooling load per unit coil length and far-field soil temperatures.

The predictions show that the ground-coupled heat pump should give best performance in coarse grained, well packed, moisture saturated soil. Worst performance was predicted to occur in fine grained, loose packed, dry soil.

The model was also used to predict the maximum performance of a well designed ground-coupled heat pump in the Knoxville area. The maximum predicted seasonal performance factor was 2.04.

Disciplines
Mechanical Engineering
Degree
Master of Science
Major
Mechanical Engineering
Embargo Date
June 1, 1984
File(s)
Thumbnail Image
Name

WixStevenD_1984_OCRed.pdf

Size

4.97 MB

Format

Adobe PDF

Checksum (MD5)

6e9b1a7ff17f9b9440fc7867555b81b2


University Libraries

1015 Volunteer Boulevard
Knoxville, TN 37996
865-974-4351

Map & Directions
Donate to the Libraries
  • About
  • John C. Hodges Society
  • Speaking Volumes magazine
  • Outreach
  • Directory
  • Employment
  • Policies
  • Library Intranet
University of Tennessee power T logo

The University of Tennessee, Knoxville
Knoxville, Tennessee 37996
865-974-1000

Events
A-Z
Apply
Privacy
Map
Directory
Give to UT
Accessibility

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science