  5. Real-time Voltage Stability Monitoring and Control for Load Areas: A Hybrid Approach
Details

Real-time Voltage Stability Monitoring and Control for Load Areas: A Hybrid Approach

Date Issued
August 1, 2016
Author(s)
Hu, Fengkai  
Advisor(s)
Kai Sun
Additional Advisor(s)
Leon M. Tolbert
Fangxing Li
Xueping Li
Permanent URI
https://trace.tennessee.edu/handle/20.500.14382/25095
Abstract

This dissertation proposes a hybrid approach for real-time monitoring and controlling voltage stability of a load area fed by N tie lines. This hybrid approach integrates both simulation-based and measurement-based approaches for voltage stability assessment (VSA).


First, for measurement-based VSA (MBVSA), a new method is proposed for monitoring and control of load areas, which adopts an N+1 buses equivalent system so as to model and monitor individual tie lines of a load area compared to a traditional MBVSA method adopting a Thevenin equivalent. For each tie line, the new method solves the power transfer limit against voltage instability analytically as a function of all parameters of that equivalent, which is online identified from real-time synchronized measurements on boundary buses of the load area. Thus, this new MBVSA method can directly calculate the real-time power transfer limit on each tie line.

Second, in order to assess the voltage stability margins under an n-1 contingency, based on the proposed MBVSA method, two sensitivity analyses have been performed, which are respectively for the parameter sensitivity of the equivalent system and the sensitivity of the tie line flow under an n-1 contingency.

Third, the proposed MBVSA method implemented for both the real-time condition and potential n-1 contingencies is integrated with the simulation-based VSA approach to form a hybrid approach. The MBVSA method helps reduce the computation burden by eliminating the unimportant contingencies while the simulation-based method provides accurate information for specific “what if” scenarios such as stability limit and margin indices under n-1 contingency conditions. In addition, simulation using the model of the system can provide recommendations for preventive control if potential voltage instability is identified.

This proposed hybrid VSA approach has been validated on the NPCC (Northeast Power Coordinating Council) Large-scale Test Bed (LTB) system developed by the CURENT (Center for Ultra-Wide-Area Resilient Electric Energy Transmission Networks), and also implemented on the CURENT Hardware Test Bed (HTB) system. The effectiveness of the MBVSA in real-time monitoring and closed-loop control against voltage instability has been validated.

Subjects

Load center

N+1 buses equivalent

parameter estimation

phasor measurement un...

power transfer limit

Thevenin equivalent

voltage stability mar...

Disciplines
Power and Energy
Degree
Doctor of Philosophy
Major
Electrical Engineering
Embargo Date
January 1, 2011
File(s)
Thumbnail Image
Name

FengkaiHuPhDDissertation_final.pdf

Size

3.54 MB

Format

Adobe PDF

Checksum (MD5)

f7b5019f3ed473acc1d7cd34def20998


University Libraries

1015 Volunteer Boulevard
Knoxville, TN 37996
865-974-4351

Map & Directions
Donate to the Libraries
  • About
  • John C. Hodges Society
  • Speaking Volumes magazine
  • Outreach
  • Directory
  • Employment
  • Policies
  • Library Intranet
University of Tennessee power T logo

The University of Tennessee, Knoxville
Knoxville, Tennessee 37996
865-974-1000

Events
A-Z
Apply
Privacy
Map
Directory
Give to UT
Accessibility

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science