High Voltage Point of Load Converter for Data Center Power Supplies

Date Issued
May 1, 2016
Author(s)
Cui, Yutian  
Advisor(s)
Leon M. Tolbert
Additional Advisor(s)
Fred Wang, Daniel J. Costinett, Andrew W. Wereszczak
Abstract

With the increased cloud computing and digital information storage, the energy requirement of data centers where a large number of computer systems are housed keeps increasing. However, most of the data centers today are operated inefficiently, both economically and environmentally. Efforts including improving power delivery architecture, power conversion efficiency and thermal management have been made to increase the power delivery efficiency from grid to point of load.


In this dissertation, a new power delivery architecture, high voltage point of load (HV POL) architecture, has been proposed in order to improve power conversion and distribution efficiency for data center power supplies.

First, the conversion structure has been selected as input series and output parallel (ISOP) to fulfill the high ratio (400: 1) conversion and mitigate the step down stress of a single converter. Also, with multiple output phases, interleaving control technique can be applied to increase equivalent switching frequency and allows smaller output inductor.

Then, two different types of converter topologies have been chosen for evaluation in the ISOP structure: phase shift full bridge (PSFB) and half bridge current doubler. High efficiency driven converter design and control method have been performed on both topologies. In PSFB, the output junction capacitance of primary side devices’ impact on converter’s efficiency has been studied. For half bridge current doubler, a novel control method enabling soft switching over the entire load range with simple auxiliary circuit is proposed and verified in experiments.

A six phase ISOP connected half bridge current doubler converter was built and tested to realize the single stage 400 V to 1 V conversion. Adaptive voltage positioning (AVP) control is analyzed and performed on the ISOP system to meet the on-board power supply requirement. Also, the impact of mismatches in the ISOP connected modules are calculated and simulated for both static and dynamic performance, and it is shown that the ISOP system is relatively immune to circuit’s mismatches. Therefore, the concept of using the single stage ISOP connected converter has been shown to be feasible as a high efficiency on-board power supply with good transient performance.

Subjects

Power supplies

high step down

soft switching

adaptive voltage posi...

input series output p...

Disciplines
Power and Energy
Degree
Doctor of Philosophy
Major
Electrical Engineering
Embargo Date
January 1, 2011
File(s)
Thumbnail Image
Name

Thesis_Yutian_Cui_0119.docx

Size

12.33 MB

Format

Microsoft Word XML

Checksum (MD5)

792b821c36b3540600ac06ee2d22511a

Thumbnail Image
Name

Thesis_Yutian_Cui_0218.pdf

Size

3.64 MB

Format

Adobe PDF

Checksum (MD5)

1b99d5f25d95a29c57b9929224dd9a8d

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Privacy policy
  • End User Agreement
  • Send Feedback
  • Contact
  • Libraries at University of Tennessee, Knoxville
Repository logo COAR Notify