Repository logo
Log In(current)
  1. Home
  2. Colleges & Schools
  3. Graduate School
  4. Masters Theses
  5. Linkage Between Characteristics of Premise Plumbing Systems and Microbial Quality of Stagnant Drinking Water
Details

Linkage Between Characteristics of Premise Plumbing Systems and Microbial Quality of Stagnant Drinking Water

Date Issued
August 1, 2013
Author(s)
Frerichs, Joshua Thomas
Advisor(s)
Qiang He
Additional Advisor(s)
Chris D. Cox
John S. Schwartz
Permanent URI
https://trace.tennessee.edu/handle/20.500.14382/38380
Abstract

The length of pipe between the water main and the point of use (POU), known as premise plumbing, has a direct impact on public health. However, relatively little is known about factors that affect the microbial quality in premise plumbing. Although microbial quality typically degrades during stagnation, little research is present linking factors such as building age and level of usage to the extent to which stagnation occurs.


To gain insight into the effect of premise plumbing service age on the level of microbial contamination in stagnant drinking water, water at the POU was analyzed. It was observed with statistical significance (p<0.05) that as service age of a premise plumbing system increased so did microbial concentration in stagnant drinking water. Results also indicated that partially repiping premise plumbing systems may greatly reduce the abundance of microorganisms, again demonstrating the impact of service age on microbial quality of stagnant drinking water in premise plumbing and suggesting re-piping as a potential risk-mitigating strategy.

Two rapidly measurable parameters (free chlorine and temperature) were analyzed for their suitability in use for indicating the extent of drinking water stagnation at the POU. Because of the seasonal variability of temperature in water supply, water temperature was not found to be a suitable indicator of stagnancy. Free chlorine, however, was found to be a suitable indicator of stagnancy. Free chlorine concentrations were also linked to heterotrophic plate counts. Additionally, the effect of pipe size on free chlorine concentration after overnight stagnation was analyzed. These results were used to show flushing tap water for 15s for every 100ft of 0.5in copper piping in order to reduce microbial contamination is a simple potential risk-mitigation strategy for premise plumbing users.

Further analyses focused on the chlorine decay rates in copper pipes. Chlorine was found to decay faster in newly built premise plumbing systems than old systems and fastest in unused copper pipes. The effect of increased usage was also analyzed; increasing the usage in older premise plumbing systems decreased the chlorine decay rate while the same increase in usage in newer systems increased the chlorine decay rate.

Subjects

Drinking Water

Stagnation

Premise Plumbing

Chlorine Decay

Service Age

Heterotropic Plate Co...

Disciplines
Environmental Engineering
Degree
Master of Science
Major
Environmental Engineering
File(s)
Thumbnail Image
Name

0-Frerichs_Thesis.pdf

Size

1.32 MB

Format

Adobe PDF

Checksum (MD5)

ddd4e403effac72c372d4c19b87e23e5

Thumbnail Image
Name

Thesis__Joshua_Frerichs.pdf

Size

1.3 MB

Format

Adobe PDF

Checksum (MD5)

8480b8c019ddc4d534ed9c1d20d19884

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Privacy policy
  • End User Agreement
  • Send Feedback
  • Contact
  • Libraries at University of Tennessee, Knoxville
Repository logo COAR Notify